dimensions | 482.6mm×177.0mm×283.0mm(W×H×D) |
Normal working temperature | -40℃~70℃ |
Extreme working temperature | -40℃~85℃ |
Storage and transportation | -40℃~85℃ |
Relative humidity | 5%~95% |
Atmospheric pressure | 80kPa~106kPa |
DC working power | 220V / 110V, allowable deviation: -20%~+15% |
Remote signal input | DC110V / DC220V, passive contact input, isolated by optocoupler |
Power consumption of DC power circuit | Under normal operation, the power consumption of entire device is no more than 40W |
Sampling frequency | Standard 4000Hz (80 points/cycle) |
Sampling precision | The voltage channel meets level 0.2 |
The protection current channel meets level TPY (5P40) | |
The measurement/metering current channel meets level 0.2 | |
Even-bay sending discreteness | Even-bay sending discreteness is no more than 10μs |
Tripping action time | The tripping action time is no more than 5ms |
Input response time | The input response time (not including the anti-shake time) should be no more than 5ms |